Our Product
GSM PUMP CONTROL SYSTEM
This product used with pump to monitor the pump energy consumption, control the pump remotely by using GSM. Also it prevent from pump starter failure.This product might be applicable where large amount of pump utilized e.g. Railway colonies, Railway yards, societies, agricultural firm …etc.
 
Feature of product:
Up to 200 pumps can be monitored and controlled.
Pump setting configured from base station/office.
Energy consumption database is maintained for each pump.
Two configurable schedules are provided.
Switching ON/OFF pumps from base station by using GSM communication.
10 different types of records are maintain in database (Power on, power off, Manual on/off, Schedule on/off, Starter Tripping, Time out, Enquiry, Emergency off).
Daily and monthly reports are maintained.
 
Technical Specification:
 
System Supply: 415 Vac, 3 Phase (200vac – 530vac)
Output Contacts: Open Normally Open Contact
Output Contact Rating: 5 Amps At 230vac
Trip Time Delay: 2 – 3 Seconds
Temperature Range:

0 0c To 75 0c

GSM Modem: Quad-band EDGE Connectivity for 850, 900, 1800 and 1900MHZ frequency bands. Supports GSM, GPRS, EDGE and CSD,Full IPR protection
CURRENT SENSING RELAY
The current sensing relay is used to trip the alarm or switching functions depending upon a change in line current. It is equipped with independently adjustable high current and low current circuit closing contacts

.This product used in electrical panel in which fans are excessively used. If fan failure occurs it will give command to alarm /buzzer.
 
Feature of product:
This unit can configured up to any number of fans for each panel.
Unit will trip alarm when under and over current faults occurs. It will also trip the alarm when fan failure is there.
 
Technical Specification:
 
System Supply: 240 Vac, 1 Phase
Output Contacts: Normally Open Contact
Current Input Sensing Range: 0.05 – 2.5amp
Trip Time Delay: 2 – 3 Seconds
Cabinet Type: Din rail
Output On Indication: 3mm Led
Temperature Range: 0 0c To 75 0c
Trip Set Point: Factory Pre-Set At Approximately 1.25 Amps.Electrical Isolation Between Circuits.
SINGLE PHASE PREVENTION CIRCUIT
This product used in electrical panel to disconnect capacitor bank/step when single phasing occurred, it can avoid from over capacitive compensation in single phasing.
 
Feature of product:
It senses supply voltage and prevents the Capacitor against too low voltage conditions.
No auxiliary supply required.
Auto reset type voltage hysteresis gap for tripping on under voltage.
 
Technical Specification:
 
System Supply: 415 Vac, 3 Phase (200vac 530vac)
Output Contacts: Normally Open Contact
Output Contact Rating: 5 Amps At 230vac
Under Voltage trip: 300VAC (+- 3%)
Trip Time Delay: 2 – 3 Seconds
Reset Mode: Auto Reset
Output On Indication:

3mm LED

Trip Set Point: Factory Pre-Set At Approximately 1.25 Amps.Electrical Isolation Between Circuits.
Temperature Range: 0 0c To 75 0c
Mounting: Overall dimensions 198 (W) x 90 (L) x 60 (D) mm.
 
UNDER DEVELOPMENT STAGE
SMART ENERGY METERING AND MONITORING SYSTEM
Single phase energy meter and remotely power monitoring is designed to meter residential and small commercial energy consumers in distribution networks.
The meter is designed to offer reliable energy measurement in single phase circuit and is highly suitable for metering and remote communication purposes. It comes with large display with a range of communication options for local and remote monitoring.
The meter complies with national and international metering standards.
It is a perfect combination of well-proven metering technology and state of the art communication modems all integrated in single enclosure.
The intelligent features of detecting and recording different anomaly conditions and cover opening events make it ideal choice for revenue protection for distribution companies.
 
 
 
Technical Specification:
 
Sr.
no
Topic Description
1 Connection Type : Single Phase Two Wire
2 Accuracy : Class 1.0 IS13773, IEC 62052-11/IEC
62053-21
3 Voltage Nominal : 240(L-M)
4 Operating Voltage : 40% of nominal voltage
5 Current : 50Hz 5%
6 Power Factor Range : Zero(lag)-zero(lead)
7 frequency : 50Hz 5%
8 Starting Current : 0.4% of lb
9 Power Consumption : Voltage Circuit; Current Circuit; <1VA>
10 Temperature range : -10 to + dag. C
11 Display : Custom built LCD with back light 6+2 digit segment display for parameter
and for other indications
12 Communication
lnterfaces :
Optical port hardware compatible to IEC 62056-21 IrDA / IR Isolated RS232(RJ11) 13
13 Measured Values : Maximum demand kW
14 Billing registers : Up to last 12 months bill point registers
15 Event Logging : Current reversal ,Neutral missing ,Earth load ,Front cover open detection,
Terminal cover open detection
16 Enclosure Case : IP51
 
 
Copyright 2012 Rose Technologies design and hosted by www.ewebideas.com